GlobeCore / Products / Mineral oil processing equipment / Oil degassing, thermal oil vacuum drying / CMM-4 Mobile unit for powered transformer oil processing

CMM-4 Mobile unit for powered transformer oil processing

GlobeCore designed CMM-4 mobile unit for removal of different contaminants and water from transformer oil. Unit can provide evacuation, degassing and heating of oil filled facilities.

CMM-4 unit construction is made from metal and contains heater, vacuum chamber, vacuum pump, oil input and output pumps, two cartridge filters with a fineness of 5 microns.

The vacuum chamber serves for a thermal and vacuum purification. The assembly of a vacuum chamber facilitates the fine oil dispersion. Peculiarity of a system is a highly effective filter activator, which design gives a large oil surface for treatment. Through a side glass it is possible to observe transformer oil treatment and filter activators.

Operation modes:

  • filtration;
  • filtration with heating and thermal vacuum oil cleaning;
  • oil degassing.

Parameter Value
Oil Purification Capacity, m3/hour / gals. per hour:
  • oil degassing, nitrogenation, oil drying and oil filtration mode
4/1059.0
  • heating and filtration mode
7/1853.0
Capacity adjustment range, m3/hour / gals. per hour 0-4/0-1059.0
Processed oil parameters (after Oil Purification)*:
  • mass moisture content, g/ton, max
10
  • ISO 4406 purity class
9
  • solid particle content, g/ton, max
8
  • filtration fineness, micron
5
  • dielectric strength, kV, min
70
Oil temperature in oil heating mode, ºС/ ºF 90/184
Oil Filtration rate ≥50
Outlet pressure, Mpa 0.35
Oil output head, meters 35.0
Oil heater power, kW 55
Oil heater mean surface power, W/cm2, max 1.15
Max power consumption, kW 63
Electric power
  • voltage, V
380
  • AC frequency, Hz**
50/60
Dimensions, mm/ft
  • length
1650/5’5’’
  • width
1250/5’3’’
  • Height
1650/4’1’’
Weight, kg/lbs 50/2,033.2

Note: * initial oil parameters:

  • volumetric gas content – below 5%
  • mass moisture content – below 0.01% (100 g/ton)
  • temperature – above 0 ºС/ 32 ºF.

**All equipment sold in the USA is designed to operate on 60 Hz AC Power

  • Construction of the unit allows being installed on a truck and using on-site;
  • Сleaning the oil by thermal vacuum in one cycle;
  • Prolongs transformer service life;
  • Easy to maintain and operate.